1SDA066820R1
Giá: Liên hệ
Mã sản phẩm: 1SDA066820R1
XT1B 160 TMD 160-1600 4p F F InN=50%
General Information
-
- Extended Product Type:
- XT1B 160 TMD 160-1600 4p F F InN=50%
-
- Product ID:
- 1SDA066820R1
-
- EAN:
- 8015644694548
-
- Catalog Description:
- XT1B 160 TMD 160-1600 4p F F InN=50%
-
- Long Description:
- C.BREAKER TMAX XT1B 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 160-1600 A NEUTRAL = 50% PHASES
Categories
- Products » Low Voltage Products and Systems » Circuit Breakers » Moulded Case Circuit Breakers » Tmax XT
Ordering
-
- EAN:
- 8015644694548
-
- Minimum Order Quantity:
- 1 piece
-
- Customs Tariff Number:
- 85362090
Dimensions
-
- Product Net Width:
- 101.6 mm
-
- Product Net Height:
- 130 mm
-
- Product Net Depth / Length:
- 70 mm
-
- Product Net Weight:
- 1,383 kg
Container Information
-
- Package Level 1 Units:
- 1 piece
-
- Package Level 1 Width:
- 128 mm
-
- Package Level 1 Height:
- 135 mm
-
- Package Level 1 Depth / Length:
- 143 mm
-
- Package Level 1 Gross Weight:
- 1,452 kg
-
- Package Level 1 EAN:
- 8015644694548
Additional Information
-
- Circuit Breaker Type to be Associated:
- Power Distribution
-
- Current Type:
- AC/DC
-
- Electrical Durability:
-
120 cycles per hour
8000 cycle
-
- Mechanical Durability:
-
Nr. Operations 240 cycles per hour
Nr. Operations 25000 cycle
-
- Number of Poles:
- 4
-
- Opening Time:
-
CB with SOR 15 ms
CB with UVR 15 ms
-
- Order Multiple:
- 1 piece
-
- Power Loss:
- at Rated Operating Conditions per Pole 15 W
-
- Product Main Type:
- SACE Tmax XT
-
- Product Name:
- Moulded Case Circuit Breaker
-
- Product Type:
- CB
-
- Rated Current (In):
- 160 A
-
- Rated Frequency (f):
- 50 / 60 Hz
-
- Rated Voltage (Ur):
- 690 V
-
- Rated Impulse Withstand Voltage (Uimp):
- 8 kV
-
- Rated Instantaneous Short-Circuit Current Setting (Ii):
- 1600 A
-
- Rated Insulation Voltage (Ui):
- 800 V
-
- Rated Operational Voltage:
-
690 V AC
500 V DC
-
- Rated Service Short-Circuit Breaking Capacity (Ics):
-
(220 V AC) 25 kA
(230 V AC) 25 kA
(240 V AC) 25 kA
(380 V AC) 18 kA
(415 V AC) 18 kA
(440 V AC) 11.25 kA
(500 V AC) 8 kA
(525 V AC) 6 kA
(690 V AC) 3 kA
(250 V DC) 2 Poles in Series 18 kA
(500 V DC) 3 Poles in Series 18 kA
-
- Rated Ultimate Short-Circuit Breaking Capacity (Icu):
-
(220 V AC) 25 kA
(230 V AC) 25 kA
(240 V AC) 25 kA
(380 V AC) 18 kA
(415 V AC) 18 kA
(440 V AC) 15 kA
(500 V AC) 8 kA
(525 V AC) 6 kA
(690 V AC) 3 kA
(250 V DC) 2 Poles in Series 18 kA
(500 V DC) 3 Poles in Series 18 kA
-
- Rated Uninterrupted Current (Iu):
- 160 A
-
- Release Type:
- TM
-
- Setting Range:
- 112...160 A
-
- Standards:
- IEC
-
- Sub-type:
- XT1
-
- Terminal Connection Type:
-
Fixed Circuit-Breakers
Front
-
- Version:
- F
Certificates and Declarations (Document Number)
-
- Data Sheet, Technical Information:
- 1SDC210033D0204
-
- Declaration of Conformity - CE:
- 9AKK106713A5532
-
- Environmental Information:
- 1SDL000190R0001
-
- GL Certificate:
- 1SDL000163R0103
-
- Instructions and Manuals:
- 1SDH000719R0001
-
- LR Certificate:
- 1SDL000163R0100
Classifications
-
- ETIM 4:
- EC000228 - Power circuit-breaker for trafo/generator/installation prot.
-
- ETIM 5:
- EC000228 - Power circuit-breaker for trafo/generator/installation prot.
-
- ETIM 6:
- EC000228 - Power circuit-breaker for trafo/generator/installation prot.
-
- ETIM 7:
- EC000228 - Power circuit-breaker for trafo/generator/installation protection
-
- Object Classification Code:
- Q
-
- UNSPSC:
- 39120000
-
- WEEE Category:
- 5. Small Equipment (No External Dimension More Than 50 cm)