Main
range
Masterpact
 
product name
Micrologic
 
product or component type
Control unit
 
range compatibility
Masterpact NT06...16
Masterpact NW08...40
Masterpact NW40b...63
 
device application
Distribution
 
poles description
3P
4P
 
protected poles description
4t
3t
3t + N/2
 
network type
AC
 
network frequency
50/60 Hz
 
trip unit name
Micrologic 7.0 P
 
trip unit technology
Electronic
 
trip unit protection functions
Selective + earth-leakage protection
 
protection type
Earth leakage
Overload protection (long time)
Short time short-circuit protection
Instantaneous short-circuit protection
 
trip unit rating
630 A at 50 °C
800 A at 50 °C
1000 A at 50 °C
1250 A at 50 °C
1600 A at 50 °C
2000 A at 50 °C
2500 A at 50 °C
3200 A at 50 °C
4000 A at 50 °C
5000 A at 50 °C
6300 A at 50 °C
 
earth-leakage protection
With
 
Complementary
mounting mode
Fixed
 
long time pick-up adjustment type Ir
Adjustable 9 settings
 
long time pick-up adjustment range
0.4...1 x In
 
long time delay adjustment type
Adjustable 9 settings
 
[tr] long-time delay adjustment range
0.7…16.6 s 7.2 x Ir
0.7…24 s 6 x Ir
12.5…600 s 1.5 x Ir
 
thermal memory
20 mn
 
short-time pick-up adjustment type Isd
Adjustable 9 settings
 
[Isd] short-time pick-up adjustment range
1.5...10 x Ir
 
short-time delay adjustment type
Adjustable
 
[tsd] short-time delay adjustment range
0…0.4 s I²t=off
0.1…0.4 s I²t=on
 
instantaneous pick-up adjustment type Ii
Adjustable 9 settings
 
instantaneous pick-up adjustment range
2...15 x In
Off
 
zone selective interlocking ZSI
With
 
residual earth-leakage sensitity adjustment type
Adjustable 9 settings
 
[IΔn] residual earth-leakage sensitive adjustment
0.5…30 A
 
residual earth-leakage time delay adjustment type
Adjustable 5 settings
 
[Δt] residual earth-leakage time delay adjustment
60…800 ms
 
earth-leakage sensitivity
10 A for class A
30 A for class AC
 
communication of data
Measurement readout
Protection and alarm settings
Maintenance indicators
 
display type
Digital display
 
type of measurement
Power meter
 
Environment
ambient air temperature for operation
-25…70 °C
 
ambient air temperature for storage
-25…85 °C
 
Offer Sustainability
Sustainable offer status
Green Premium product
 
REACh Regulation  
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
 
Mercury free
Yes
 
RoHS exemption information  
China RoHS Regulation
China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
 
Environmental Disclosure  
Circularity Profile  
Contractual warranty
Warranty
18 months

Sản phẩm khác