LC1K0610P7

LC1K0610P7
LC1K0610P7

Giá: Liên hệ

Mã sản phẩm: LC1K0610P7

Main
range
TeSys
 
product or component type
Contactor
 
product name
TeSys K
 
device short name
LC1K
 
device application
Control
 
contactor application
Motor control
 
Complementary
utilisation category
AC-3
AC-4
 
poles description
3P
 
power pole contact composition
3 NO
 
[Ue] rated operational voltage
Power circuit: 690 V AC 50/60 Hz
Signalling circuit: <= 690 V AC 50/60 Hz
 
[Ie] rated operational current
6 A at <= 440 V AC AC-3 for power circuit
 
control circuit type
AC at 50/60 Hz
 
[Uc] control circuit voltage
230 V AC 50/60 Hz
 
motor power kW
1.5 kW at 220...230 V AC 50/60 Hz AC-3
2.2 kW at 380...415 V AC 50/60 Hz AC-3
3 kW at 440 V AC 50/60 Hz AC-3
3 kW at 480 V AC 50/60 Hz AC-3
3 kW at 500...600 V AC 50/60 Hz AC-3
3 kW at 660...690 V AC 50/60 Hz AC-3
1.5 kW at 400 V AC 50/60 Hz AC-4
 
auxiliary contact composition
1 NO
 
[Uimp] rated impulse withstand voltage
8 kV
 
overvoltage category
III
 
[Ith] conventional free air thermal current
20 A (at 50 °C) for power circuit
10 A (at 50 °C) for signalling circuit
 
Irms rated making capacity
110 A AC for power circuit conforming to NF C 63-110
110 A AC for power circuit conforming to IEC 60947
110 A AC for signalling circuit conforming to IEC 60947
 
rated breaking capacity
110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
110 A at 220...230 V conforming to IEC 60947
110 A at 380...400 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947
 
[Icw] rated short-time withstand current
90 A 50 °C - 1 s for power circuit
85 A 50 °C - 5 s for power circuit
80 A 50 °C - 10 s for power circuit
60 A 50 °C - 30 s for power circuit
45 A 50 °C - 1 min for power circuit
40 A 50 °C - 3 min for power circuit
20 A 50 °C - >= 15 min for power circuit
80 A - 1 s for signalling circuit
90 A - 500 ms for signalling circuit
110 A - 100 ms for signalling circuit
 
associated fuse rating
25 A gG at <= 440 V for power circuit
25 A aM for power circuit
10 A gG for signalling circuit conforming to IEC 60947
10 A gG for signalling circuit conforming to VDE 0660
 
average impedance
3 mOhm - Ith 20 A 50 Hz for power circuit
 
[Ui] rated insulation voltage
Power circuit: 600 V conforming to UL 508
Power circuit: 690 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-5-1
Signalling circuit: 600 V conforming to UL 508
Power circuit: 600 V conforming to CSA C22.2 No 14
Signalling circuit: 600 V conforming to CSA C22.2 No 14
 
insulation resistance
> 10 MOhm for signalling circuit
 
inrush power in VA
30 VA (at 20 °C)
 
hold-in power consumption in VA
4.5 VA (at 20 °C)
 
heat dissipation
1.3 W
 
control circuit voltage limits
Operational: 0.8...1.15 Uc (at <50 °C)
Drop-out: 0.2...0.75 Uc (at <50 °C)
 
connections - terminals
Screw clamp terminals 1 cable(s) 1.5…4 mm²solid
Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1.5…4 mm²solid
Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
 
maximum operating rate
3600 cyc/h
 
auxiliary contacts type
type instantaneous 1 NO
 
signalling circuit frequency
<= 400 Hz
 
minimum switching current
5 mA for signalling circuit
 
minimum switching voltage
17 V for signalling circuit
 
mounting support
Rail
Plate
 
tightening torque
1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2
1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
 
operating time
10...20 ms coil de-energisation and NO opening
10...20 ms coil energisation and NO closing
 
safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
 
non overlap distance
0.5 mm
 
mechanical durability
10 Mcycles
 
electrical durability
1.3 Mcycles 6 A AC-3 at Ue <= 440 V
 
mechanical robustness
Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
 
height
58 mm
 
width
45 mm
 
depth
57 mm
 
net weight
0.18 kg
 
Environment
standards
BS 5424
IEC 60947
NF C 63-110
VDE 0660
 
product certifications
UL
CSA
 
IP degree of protection
IP2x conforming to VDE 0106
 
protective treatment
TC conforming to IEC 60068
TC conforming to DIN 50016
 
ambient air temperature for storage
-50…80 °C
 
operating altitude
2000 m without
 
flame retardance
V1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
 
Offer Sustainability
Sustainable offer status
Green Premium product
 
REACh Regulation  
EU RoHS Directive  
Mercury free
Yes
 
RoHS exemption information  
China RoHS Regulation
China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
 
Environmental Disclosure  
Circularity Profile  
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
 
Contractual warranty
Warranty
18 months

Sản phẩm khác